Using the Treon Magnetic Mount Adapter enables attaching Treon Industrial Node to uneven surfaces and without any opening for a bolt. The Treon Industrial Node will be pre-fixed by a magnet and the final​ installation must then be done with a suitable glue. It is possible to manually align the Treon Industrial Node.

The installation requires a Treon Magnetic Mount Adapter, epoxy, and a surface of 32 mm diameter.

What you need

For this installation method you will need:

  • Treon Magnetic Mount Adapter
  • Silicone grease
  • Glue (Loctite EA 3450, Loctite HY 4070 or other suitable glue)
  • Torque wrench

Step 1: Apply Silicon Grease

Apply and carefully spread the silicon grease to the Treon Magnetic Mount Adapter’s top surface. This is the surface opposite to the magnet surface.

If you are unsure which surface is the right one, test the magnetic surface of the adapter with a metal surface and then choose the opposite surface for this step.

Legacy illustration

Legacy illustration

Legacy illustration

Legacy illustration

Fig.: Apply grease to clean surface Fig.: Apply around the thread hole Fig.: Spread with finger
Fig.: Whole surface of adaptershould be covered

Step 2: Connect Magnetic Mount Adapter to Industrial Node

Take the Magnetic Mount Adapter and carefully screw it to the Industrial Node. The greased surface should point toward the Industrial Node, and the magnetic side away from the Node.

Fig.: Take the Epoxy Mount Adapter Fig.: Screw in all the way

Step 3: Tighten

Set the torque in the torque wrench to exactly 8 Nm. The SW size is 30 mm.

Hold the Industrial Node with the SW 30 spanner or wrench and carefully tighten the Magnetic Mount Adapter.

Fig.: Tighten with torque wrench

Step 4: Clean Machine Surface

Now carefully clean the surface of the machine where the Industrial Node should be attached.

Step 5: Apply the Glue

Prepare the glue and then apply it to the surface of your machine according to the instructions of the glue manufacturer.

Fig.: Take the epoxy glue Fig.: Mix on disposable surface Fig.: Mix both phases
Fig.: Ready when fully mixed Fig.: Apply glue to machine surface Fig.: Spread glue evenly

Please note: If you use a an epoxy glue that gets mixed in the nozzle, like the Loctite HY 4070, you can apply directly to the machine surface.

Step 6: Attach Industrial Node to Machine

Place the Treon Industrial Node on top of the glue. Now align the node so that its axis​ points directly toward either the drive or the non-drive end of the machine.​

Fig.: Attach Treon Industrial Node to machine

Let the glue harden fully before turning on the machine.

The Treon Industrial Node or Treon Industrial Node 6 is now fully installed!